UltraSense Detection and Monitoring

UltraSense Detection and Monitoring

Detect the conditions that precede a fire.

UltraSense™ is Fireaway’s modular sensor platform. It monitors temperature, gas, power, and environment in critical equipment so operators can intervene before a fault becomes a fire.

What it is

A modular sensor platform for critical equipment.

UltraSense is an environmental monitoring and early-warning detection system. A networked base unit connects the sensors each site requires, selected from more than 80 sensor types, and reports to the owner’s monitoring, building management, or control system. Sensors connect with standard network cabling, hubs expand capacity, and sensors can be added later as requirements change.

UltraSense was introduced by Fireaway in 2025 and is supplied and supported from Minnetonka, Minnesota. Product details are on ultrasense.net.

How it detects

Heat, gas, power, and environment.

  • Heat. Thermal imaging and infrared spot sensors monitor connections, breakers, and bus bars for hot spots.
  • Gas. Flammable, toxic, and corrosive gas sensors cover hydrogen, methane, carbon monoxide, hydrogen fluoride, refrigerants, and other gases. The Flammable Gas Sensor measures flammable gas from 0 to 100 percent of the lower explosive limit and detects the off-gassing that precedes lithium-ion thermal runaway.
  • Power. Power quality sensors track interruptions, voltage sags and swells, harmonic distortion, and frequency fluctuations that stress equipment.
  • Environment. Temperature and humidity, water leak, dust, vibration, and corrosion sensors track the conditions that degrade insulation and electronics over time.

The catalog also includes smoke, airflow, air pressure, grounding, and lightning sensors, plus door, motion, light, and sound sensors for site security, so one platform covers fire, environmental, and security monitoring.

The flammable gas sensor

Detect off-gas before thermal runaway.

Failing lithium-ion cells release flammable gas before they ignite. The UltraSense Flammable Gas Sensor detects that release, giving operators time to isolate a battery rack or shut down a system before thermal runaway. It measures 11 flammable gases, including hydrogen, methane, and propane, reports a volatile organic compound index, and has a T90 response time under 30 seconds.

The sensor uses a spectrometer-based sensing element that does not require periodic calibration with reference gas; a periodic bump test is recommended in critical environments. It is ETL listed to UL 2075 and carries California State Fire Marshal listing. Three on-board relays (two alarm, one fault) signal to a fire alarm panel or building management system.

Where it is used

Energy storage, switchgear, data centers, solar, and wind.

Continuous condition monitoring of electrical equipment supports the maintenance programs described in NFPA 70B and the requirements of NFPA 855 for energy storage systems.

Integration

Open protocols, existing panels.

The base unit communicates over standard Ethernet and supports SNMP, Modbus TCP, and MQTT, with Modbus RTU available as an expansion. Alarms can be sent by email, SMS, or SNMP trap, and relay outputs can trigger a fire alarm panel, shut down equipment, or shed load. UltraSense works alongside existing fire alarm systems; it does not replace them.

Prevent, detect, suppress

Prevention and detection, then suppression.

UltraSense covers the prevention and detection stages of fire protection. Stat-X® condensed aerosol covers suppression. Used together, an UltraSense gas or thermal alarm provides early warning and, if conditions escalate, can initiate Stat-X discharge through a listed releasing panel. Fireaway supplies and supports both, so owners have one source for the full protection sequence. See Stat-X condensed aerosol fire suppression.

Listings

Safety listed sensors and base units.

Sensors are tested by UL to UL 61010, the standard for electrical measurement and control equipment. Base units and hubs meet UL 62368. The Flammable Gas Sensor is additionally ETL listed to UL 2075 and carries CE marking and EN 50270 and EN 61010 certification. Fireaway operates under ISO 9001:2015 and ISO 14001:2015 certified management systems.

Next steps

Learn more.

Contact

Speak with a fire protection expert.